The H-Factor

Reducing Entropy

Recent Posts

Welcome

Recently our previous blog service (Typepad) ended their business – so, we have a new home. It will take a bit to get images back and displaying properly, but we are working on it! Final pageview count of original Typepad blog: 387,232

Using a Non-Standard Pipe Type in HydraCALC

A customer called today asking how to enter a 1″ black plastic underground pipe for the calc. This particular situation sounded unique enough that I did not tell him to add that pipe type to our database, as I would have if he expected to see this pipe type used repeatedly. I told him to…

Using the Hydratec Software Download Area

Hydratec uses ShareFile to distribute our software installs and updates. New customers, or those without access, must request access to be able to get at these downloads. Access is only available to customers with a Hydratec subscription or those on an update plan. You can access the download area and request access by picking the…

June 2010
M T W T F S S
 123456
78910111213
14151617181920
21222324252627
282930  

Ws2

This problem is not what it might seem at first glance. While it is true that the water supply block may not be at the end of a pipe, it is more likely that the riser nipples somewhere in the grid (it is usually seen in a grid) are set to User Specified when they should be set to Computer Generated.

Elevating the system to 3D resulted in the following piping configuration:

Tpnf

Something is obviously wrong, here.

The grid that had this problem had branch lines that run with the slope of the building. Both mains were tied into the branch lines with User Specified riser nipples. The problem with doing that is that is it extremely difficult to calculate the exact length that the riser nipples will be to meet the differing elevations. The solution is to make the riser nipples on one side of the grid Computer Generated. The quickest way to change these is to use the Edit Riser Nipple command on the Riser Nipple flyout of the Piping toolbar. Or type in ERN.

Ern1

Pick the first button – Change to Comp Gen/User Spec. Then Pick Computer Generated and pick Apply.

Ern2

Select the riser nipples to change. You will see a magenta circle around the selected riser nipples. This tells you that those riser nipples will have their length Computer Generated.